5 · Load Build-up

Dead loads from IS 875 Part 1, imposed loads from Part 2 by room occupancy, factored by 1.5 for the limit state of collapse (IS 456 Table 18).

Dead load build-up

IS 875 Part 1 — unit weights of materials
ComponentFloor kN/m²Roof kN/m²
Slab self weight — 125 mm × 25 kN/m³3.133.13
Floor finish (screed + tiles)1.000.50
Ceiling plaster0.250.25
Partition allowance (light partitions)1.000.00
Services / false ceiling0.250.00
Waterproofing (roof only)0.001.50
Total dead load5.635.38
Imposed load2.003.001.50
Service load (DL + LL)7.638.636.88
Factored 1.5 (DL + LL)11.4412.9410.31
Imposed loads are no longer averaged: every slab panel, beam and column takes the imposed load of the room that actually sits on it (IS 875 Part 2 Table 1). The service and factored rows above therefore show the range across your rooms.

Imposed load room by room

IS 875 Part 2 Table 1 — applied panel by panel, not averaged
RoomOccupancyImposed kN/m²
F1 · LivingLiving / Drawing room2.00
F1 · DiningDining room2.00
F1 · KitchenKitchen2.00
F1 · Bedroom 1Bedroom2.00
F1 · StaircaseStaircase3.00
F1 · ToiletToilet / Bathroom2.00
F2 · Master bedroomBedroom2.00
F2 · Bedroom 2Bedroom2.00
F2 · Bedroom 3Bedroom2.00
F2 · StudyStudy / Home office2.50
F2 · LandingPassage / Corridor / Lobby3.00
F2 · Toilet 1Toilet / Bathroom2.00
F2 · BalconyBalcony3.00

Governing factored load on each slab panel

1.5 (DL + LL of the room on that panel)
PanelGoverning roomLL kN/m²wu kN/m²
A1-B2Master bedroom2.0011.44
A2-B3Bedroom 22.0011.44
A3-B4Bedroom 32.0011.44
B1-C2Study2.5012.19
B2-C3Landing3.0012.94

Wall loads on beams

Line load = (t·γ + 2·plaster) × clear height × opening factor
External wall
11.47kN/m
Internal wall
6.31kN/m
Parapet
2.70kN/m
Clear height under the beam = 2.75 m · plaster taken at 20.4 kN/m³.

Adjust the assumptions

Each slab panel is designed for its own factored load — currently 11.4412.94 kN/m² across the panels. If you raise finishes or imposed loads, every slab, beam, column and footing downstream updates immediately.
Built-up105.0 m²Columns11Governing column264 kNConcrete38.2 m³Steel2.30 t11 checks need attention